Review of Modern Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers

نویسنده

  • Tapan K. Saha
چکیده

Cellulosic paper and oil insulation in a transformer degrade at higher operating temperatures. Degradation is accelerated in the presence of oxygen and moisture. Power transformers being expensive items need to be carefully monitored throughout its operation. Well established time-based maintenance and conservative replacement planning is not feasible in a current market driven electricity industry. Condition based maintenance and online monitoring are now gaining importance. Currently there are varieties of chemical and electrical diagnostic techniques available for insulation condition monitoring of power transformers. This paper presents a description of commonly used chemical diagnostics techniques along with their interpretation schemes. A number of new chemical techniques are also described in this paper. In recent times a number of electrical diagnostic techniques have gained exceptional importance to the utility professionals. Among these techniques polarisationrdepolarisation current measurement, return voltage measurement and frequency domain dielectric spectroscopy at low frequencies are the most widely used. This paper describes analyses and interpretation of these techniques for transformer insulation condition assessment. Index Terms — Insulation condition, transformer diagnostics, transformer ageing, dissolved gas analysis, furan analysis, degree of polymerization, oil insulation, cellulose paper, return voltage, polarisation current, depolarisation current, online monitoring, condition based monitoring.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Electrical-Based Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers

The condition of the internal cellulosic paper and oil insulation are of concern for the performance of power transformers. Over the years, a number of methods have been developed to diagnose and monitor the degradation/aging of the transformer internal insulation system. Some of this degradation/aging can be assessed from electrical responses. Currently there are a variety of electrical-based ...

متن کامل

Condition Monitoring Techniques of Power Transformers: A Review

Power transformers provide a vital link between the generation and distribution of produced energy. Such static equipment is subjected to abuse during operation in generation and distribution stations and leads to catastrophic failures. This paper reviewed the techniques in the field of condition monitoring of power transformers in recent years. Transformer monitoring and diagnosis are the effe...

متن کامل

Raman Spectral Characteristics of Oil-Paper Insulation and Its Application to Ageing Stage Assessment of Oil-Immersed Transformers

The aging of oil-paper insulation in power transformers may cause serious power failures. Thus, effective monitoring of the condition of the transformer insulation is the key to prevent major accidents. The purpose of this study was to explore the feasibility of confocal laser Raman spectroscopy (CLRS) for assessing the aging condition of oil-paper insulation. Oil-paper insulation samples were ...

متن کامل

Integrated Management System for Testing, Monitoring and Diagnostic of Power Transformer Insulation

Power transformers are the most complex, important and critical components of the transition and distribution power systems. Insulation system is the key component of life extension, better availability and higher reliability of a transformer. In order to achieve both decreasing operational cost and reliable service conditionbased maintenance is needed. Monitoring and diagnostic methods and tec...

متن کامل

Some Precautions for the Field Users of PDC Measurement for Transformer Insulation Condition Assessment

The need for economic, reliable and effective delivery of electric power has lead to the search for new, efficient and effective methods for diagnosing the insulation of the HV equipments in the industries all over the world. One of the methods currently being investigated as a potential nondestructive diagnostic tool for condition monitoring of the oilpaper insulation of power transformers is ...