Synchronous machine performance under geomagnetic disturbances
نویسندگان
چکیده
Geomagnetic disturbances (GMDs) are known to disturb power system equipment performance. The danger is associated with geomagnetically induced currents (GICs) occurring at the Earth's surface during GMD. GICs do not endanger operation conditions by themselves. main challenge posed states change in provoked GIC flow. primary avenue of blackout caused GMDs through transformers. This, turn, can impair other such as synchronous machines. Modern powerful machines designed and engineered cope negative impacts GMDs. Moreover, actual legal norms inadequate this case. Enhancing grid's resiliency an event highly interesting industry. physical processes machine windings triggered limitations brought grid operations described. First, idea impact on analysis performed second section. In end, response under studied.
منابع مشابه
Optimal Transmission Line Switching under Geomagnetic Disturbances
In recent years, there have been increasing concerns about how geomagnetic disturbances (GMDs) impact electrical power systems. Geomagnetically-induced currents (GICs) can saturate transformers, induce hot spot heating and increase reactive power losses. These effects can potentially cause catastrophic damage to transformers and severely impact the ability of a power system to deliver power. To...
متن کاملA New Method for Computation of Axial Flux Permanent Magnet Synchronous Machine Inductances under Saturated Condition
Accurate computing of the saturated inductances of Permanent Magnet Synchronous Machine (PMSM) is very important during the design process. In this paper, a new method is presented based on the B-H characteristic of the stator material and unsaturated inductances formulations. This method is used to calculate the saturated inductances of the axial flux PMSM. The synchronous inductance and all o...
متن کاملDisturbances in the US electric grid associated with geomagnetic activity
Large solar explosions are responsible for space weather that can impact technological infrastructure on and around Earth. Here, we apply a retrospective cohort exposure analysis to quantify the impacts of geomagnetic activity on the US electric power grid for the period from 1992 through 2010. We find, with more than 3r significance, that approximately 4% of the disturbances in the US power gr...
متن کاملApplication to Adaptive Control to Synchronous Machine Excitation
Self-tuning adaptive control technique has the advantage of being able to track the system operating conditions so that satisfactory control action can always be produced. Self-tuning algorithms can be implemented easily. Because the power systems are usually time varying non-linear systems and their parameters vary, adaptive controllers are very suitable for power systems. Characteristics of a...
متن کاملEccentricity Fault Diagnosis Studying for a Round Rotor Synchronous Machine
The paper presents a mathematical base modeling combined to Modified-Winding -Function-Approach (MWFA) for eccentricity fault detection of a round-rotor synchronous machine. For this aim, a 6-pole machine is considered, and the machine inductances are computed by MWFA in healthy and also under eccentricity fault. A numerical discrete-time method has been proposed to machine modeling in voltage-...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
ژورنال
عنوان ژورنال: High voltage
سال: 2021
ISSN: ['2397-7264', '2096-9813']
DOI: https://doi.org/10.1049/hve2.12107