Application of Fuzzy Logic in Fault Diagnosis in Transformers using Dissolved Gas based on Different Standards

نویسندگان

  • Rahmatollah Hooshmand
  • Mahdi Banejad
چکیده

One of the problems in fault diagnosis of transformer based on dissolved gas, is lack of matching the result of fault diagnosis of different standards with the real world. In this paper, the result of the different standards is analyzed using fuzzy and the result is compared with the empirical test. The comparison between the suggested method and existing methods indicate the capability of the suggested method in on-line fault diagnosis of the transformers. In addition, in some cases the existing standards are not able to diagnose the fault. In theses cases, the presented method has the potential of diagnosing the fault. The information of three transformers is used to the show the capability of the suggested method in diagnosing the fault. The results validate the capability of the presented method in fault diagnosis of the transformer. Keywords—Fault Diagnosis of Transformer, Dissolved Gas, Fuzzy Logic.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

ارائه یک سیستم ترکیبی جدید در تشخیص نوع خطا در ترانسفورماتورهای قدرت براساس مقادیر گازهای حل شده در روغن

Transformers are one of the important and at the same time expensive components of power systems. On timely diagnosis of fault in such systems is still among the researchers interest. Fault diagnosis of transformers based on the dissolved gas analysis is a new technique in the field of fault diagnosis of power transformers. IEC, Roger’s and Dornenburg techniques are the mostly used techni...

متن کامل

Analysis of Power Transformer using fuzzy expert and neural network system

Power transformers being the major apparatus in a power system, thus the assessment of transformer operating condition and lifespan have obtained crucial significance in latest years. Dissolved gas analysis (DGA) is a sensitive and reliable technique for the detection of incipient fault condition within oil-immersed transformers, which provides the basis of diagnostic evaluation of equipment he...

متن کامل

Development of Dissolved Gas Analysis Using ANFIS

This paper proposes the application of Adaptive Neuro-Fuzzy Inference System to improve the diagnosis accuracy of dissolved gas analysis for classification of different types of incipient faults in oil immersed power transformers. The proposed method integrated the capabilities of neural network to the robustness of fuzzy logic system for the effectiveness to be embedded in the network structur...

متن کامل

Fuzzy Decision on Transformer Fault Diagnosis using Dissolved Gas Analysis and IEC Ratio Codes

This paper emphasizes on the use of fuzzy approach in dealing with the incipient fault conditions of power transformer. DGA (Dissolved Gas in Oil Analysis) cannot provide better fault diagnosis results when multiple faults are involved. The boundary values specified by the ratio methods are of limited concern .Considering the limitations of convergence of the conventional neural networks in the...

متن کامل

Intuitionistic Fuzzy Expert System based Fault Diagnosis using Dissolved Gas Analysis for Power Transformer

In transformer fault diagnosis, dissolved gas analysis (DGA) is been widely employed for a long period and numerous methods have been innovated to interpret its results. Still in some cases it fails to identify the corresponding faults. Due to the limitation of training data and non-linearity, the estimation of key-gas ratio in the transformer oil becomes more complicated. This paper presents I...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2012