Pole-to-Ground Fault Analysis and Fast Protection Scheme for HVDC Based on Overhead Transmission Lines
نویسندگان
چکیده
Flexible direct current (DC) transmission network technology is an effective method for large capacity clean energy access to power grids, but the DC short-circuit fault detection for it is a difficult problem. In this paper, the pole-to-ground fault transient characteristics in a multi-terminal DC power grid, based on overhead transmission lines and DC circuit breakers, are analyzed firstly. Then, a fast protection scheme is proposed according to the fault transient characteristics. Only local information is utilized for fault detection and location in the proposed scheme. Moreover, the scheme is verified to have the advantages of fast action speed, high reliability and the ability to resist the transition resistance. A four terminal DC power grid model based on actual engineering parameters is established in PSCAD/EMTDC, and the validity of the protection scheme under different fault conditions is verified by simulation results.
منابع مشابه
Research of Bipolar HVDC Transmission Lines based on Traveling Wave Differential Protection
The principle of the traveling wave based differential protection for bipolar HVDC transmission lines is proposed in the paper. Unlike the traditional current differential protection, the quantity of current is replaced by the quantity of the traveling wave for comparison. The traveling wave at the remote end is transferred to the local end for comparison to the local traveling wave. For the bi...
متن کاملFault Current Characterisation in VSC-based HVDC Systems
The DC-side line faults in high-voltage direct-current (HVDC) systems utilising voltage-source converters (VSCs) are a major concern for multi-terminal HVDC systems in which complete isolation of the faulted system is not a viable option. A number of challenges are posed by both pole-to-pole and pole-to-ground faults including the presence of very fast and high amplitude discharge current from ...
متن کاملProtection Scheme of Power Transformer Based on Time–Frequency Analysis and KSIR-SSVM
The aim of this paper is to extend a hybrid protection plan for Power Transformer (PT) based on MRA-KSIR-SSVM. This paper offers a new scheme for protection of power transformers to distinguish internal faults from inrush currents. Some significant characteristics of differential currents in the real PT operating circumstances are extracted. In this paper, Multi Resolution Analysis (MRA) is use...
متن کاملThe Applicability of Traditional Protection Methods to Lines Emanating from VSC-HVDC Interconnectors and a Novel Protection Principle
Voltage source converter (VSC)-based high voltage direct current (VSC-HVDC) interconnectors can realize accurate and fast control of power transmission among AC networks, and provide emergency power support for AC networks. VSC-HVDC interconnectors bring exclusive fault characteristics to AC networks, thus influencing the performance of traditional protections. Since fault characteristics are r...
متن کاملOne Terminal Digital Algorithm for Adaptive Single Pole Auto-Reclosing Based on Zero Sequence Voltage
This paper presents an algorithm for adaptive determination of the dead timeduring transient arcing faults and blocking automatic reclosing during permanent faults onoverhead transmission lines. The discrimination between transient and permanent faults ismade by the zero sequence voltage measured at the relay point. If the fault is recognised asan arcing one, then the third harmonic of the zero...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
دوره شماره
صفحات -
تاریخ انتشار 2017