The aim of this paper is to identify an optimum control strategy of three-phase shunt active filters to minimize the total harmonic distortion factor of the supply current. A classical PIPI cascade control solution of the output current of the active filter and the voltage across the DC capacitor based on Modulus–Optimum criterion is taken into consideration. The control system operation has been simulated using Matlab-Simulink environment and the results agree with the theoretical expectation. It is shown that there is an optimum value of the DC-bus voltage which minimizes the supply current harmonic distortion factor. It corresponds to the equality of the apparent power at the output of the active filter and the apparent power across the capacitor. Finally, predicted results are verified experimentally on a MaxSine active power filter. Keywords—Active filtering, Controller tuning, Modulus Optimum criterion, Optimum control.
منابع مشابه
Compensation Strategies for Shunt Active Power Filter in Single- and Three-Phase Systems: Different Formulation, Comparison and Evaluation
متن کامل
Mitigation of Switching Harmonics in Shunt Active Power Filter Based on Variable Structure Control Approach
This paper presents a novel control approach used in shunt active power filter based on variable structure control combined with Random PWM technique (RVSC) that provides robust, fast, and more favorable performance for active power filter. This control strategy is compared with two other strategies to show the effectiveness of the introduced methods; pulse width modulated proportional-integral...
متن کاملارائۀ روش کنترلی جدید برای فیلترهای اکتیو موازی در سیستمهای سهفاز چهارسیمه بهمنظور جبرانسازی هارمونیکها، نامتعادلی و توان راکتیو
In this paper, a novel control strategy for a Shunt Active Power Filter (shunt-APF) is proposed. In the proposed control strategy which is based on a new application of the instantaneous reactive power theory, the current injected by the shunt-APF is capable of compensation for the reactive component, the harmonic components and also unbalance of the load current. In this strategy, the shunt-AP...
متن کاملA Hybrid Control Method for Stable Operation of Active Power Filters in Three-Phase Four-Wire Networks
The main goal of this study is the use of Lyapunov’s stability theory to a three-phase four-wire shunt active power filter (SAPF), since this method has been applied effectively to other areas of converter. The dynamic model of the SAPF is first established, after that, a combination of fuzzy tracking control and Lyapunov function is suggested in order to impose a desired transient waveform on ...
متن کاملA Novel Reference Current Calculation Method for Shunt Active Power Filters using a Recursive Algebraic Approach
This paper presents a novel method to calculate the reference source current and the referencecompensating current for shunt active power filters (SAPFs). This method first calculates theamplitude and phase of the fundamental load current from a recursive algebraic approach blockbefore calculating the displacement power factor. Next, the amplitude of the reference mains currentis computed with ...