A ventilation intervention study in classrooms to improve indoor air quality: the FRESH study

نویسندگان

  • Jeannette TM Rosbach
  • Machiel Vonk
  • Frans Duijm
  • Jan T van Ginkel
  • Ulrike Gehring
  • Bert Brunekreef
چکیده

BACKGROUND Classroom ventilation rates often do not meet building standards, although it is considered to be important to improve indoor air quality. Poor indoor air quality is thought to influence both children's health and performance. Poor ventilation in The Netherlands most often occurs in the heating season. To improve classroom ventilation a tailor made mechanical ventilation device was developed to improve outdoor air supply. This paper studies the effect of this intervention. METHODS The FRESH study (Forced-ventilation Related Environmental School Health) was designed to investigate the effect of a CO2 controlled mechanical ventilation intervention on classroom CO2 levels using a longitudinal cross-over design. Target CO2 concentrations were 800 and 1200 parts per million (ppm), respectively. The study included 18 classrooms from 17 schools from the north-eastern part of The Netherlands, 12 experimental classrooms and 6 control classrooms. Data on indoor levels of CO2, temperature and relative humidity were collected during three consecutive weeks per school during the heating seasons of 2010-2012. Associations between the intervention and weekly average indoor CO2 levels, classroom temperature and relative humidity were assessed by means of mixed models with random school-effects. RESULTS At baseline, mean CO2 concentration for all schools was 1335 ppm (range: 763-2000 ppm). The intervention was able to significantly decrease CO2 levels in the intervention classrooms (F (2,10) = 17.59, p < 0.001), with a mean decrease of 491 ppm. With the target set at 800 ppm, mean CO2 was 841 ppm (range: 743-925 ppm); with the target set at 1200 ppm, mean CO2 was 975 ppm (range: 887-1077 ppm). CONCLUSIONS Although the device was not capable of precisely achieving the two predefined levels of CO2, our study showed that classroom CO2 levels can be reduced by intervening on classroom ventilation using a CO2 controlled mechanical ventilation system.

برای دانلود رایگان متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

An Assessment of Indoor Air Quality and Thermal Comfort in Educational Spaces (Case Study: Girls' High Schools in Arak, Iran)

As s‌tudents spend one-third of their time at school, their health, comfort, and productivity are mos‌tly influenced by thermal condition and indoor air quality of classrooms. Regarding that manual window-opening is a common way for providing fresh air in classes and s‌tudents aren't allowed to change their uniform, position or control the windows during the lesson hours, providing thermal comf...

متن کامل

Energy-efficient air quality control in school classrooms

The aim of the present work is to maximize indoor environmental quality (IEQ), in particular air quality, and energy performance in schools, when having different ventilation alternatives combined with carbon dioxide feedback. In this effort, trial measurements and energy simulations were conducted to predict and compare the indoor environmental and energy performance in an otherwise similar sc...

متن کامل

Natural Ventilation: Analysis of Indoor Airflow in an Assumed Cubic Building with Opposite Openings by CFD Investigations

The natural ventilation is an easy way to exchange the indoor polluted warm air with outdoor fresh air. The wind power injects outdoor fresh air into the building. A good indoor air current and subsequently a proper exhaust depend on the openings’ conditions and their situations. A serious architectural question is under what conditions of the openings the wind-cross ventilation can be effectiv...

متن کامل

Ventilation Positive Pressure Intervention Effect on Indoor Air Quality in a School Building with Moisture Problems

This case study investigates the effects of ventilation intervention on measured and perceived indoor air quality (IAQ) in a repaired school where occupants reported IAQ problems. Occupants' symptoms were suspected to be related to the impurities leaked indoors through the building envelope. The study's aim was to determine whether a positive pressure of 5-7 Pa prevents the infiltration of harm...

متن کامل

بررسی آلاینده های شاخص هوای داخل و خارج منازل مسکونی شهری

Background and purpose: Indoor air pollution in developing countries is considered as one of the main problems in healthcare. This study aimed at investigating the levels of indoor/outdoor air pollutants in Khorramabad during autumn and winter 2012. Materials and methods: In a cross-sectional study, nine gas concentrations and particulate pollutants were measured using air pollution measuring ...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

عنوان ژورنال:

دوره 12  شماره 

صفحات  -

تاریخ انتشار 2013