Intermittent use of copper-silver ionization for Legionella control in water distribution systems: a potential option in buildings housing individuals at low risk of infection.

نویسندگان

  • Z Liu
  • J E Stout
  • M Boldin
  • J Rugh
  • W F Diven
  • V L Yu
چکیده

One copper-silver ionization system was sequentially installed onto the hot-water recirculation lines of two hospital buildings colonized with Legionella pneumophila, serogroup 1. A third building with the same water supply and also colonized with Legionella served as a control. Four weeks after activation of the system, distal site positivity for Legionella in the first test building dropped to zero. After operating for 16 weeks, the system was disconnected and installed onto the second test building. Twelve weeks of disinfection reduced the distal site positivity for Legionella in the second test building to zero. Legionella recolonization did not occur in the first test building for 6-12 weeks and in the second test building for 8-12 weeks after inactivation of the system. The control building remained Legionella-positive throughout the experimental period. A significantly higher copper concentration was found in the biofilm taken from a sampling device than in that from water. This is likely to be the reason that the copper-silver ionization system had the residual effect of preventing early recolonization. Our study raises the possibility that one copper-silver unit could be rotated among several buildings to maintain a Legionella-free environment. Such an approach may be cost-effective for buildings housing individuals at low risk for contracting legionnaires' disease.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Efficacy of copper-silver ionization in controlling biofilm- and plankton-associated waterborne pathogens.

The study was to determine the efficacy of copper-silver ionization against the formation of Pseudomonas aeruginosa, Stenotrophomonas maltophilia, and Acinetobacter baumannii in biofilms and planktonic phases. At concentrations below the EPA limits, ionization has potential to control the three waterborne pathogens, in addition to Legionella, in hospital water systems for nosocomial infection c...

متن کامل

Impact of copper and silver ionization on fungal colonization of the water supply in health care centers: implications for immunocompromised patients.

Copper and silver ionization is a well-recognized disinfection method to control Legionella species in water distribution systems in hospitals. These systems may also serve as a potential indoor reservoir for fungi. The prevalence of fungi was significantly lower in ionized than in nonionized water samples from health care facilities. The clinical consequences of this finding require further in...

متن کامل

Experiences of the first 16 hospitals using copper-silver ionization for Legionella control: implications for the evaluation of other disinfection modalities.

BACKGROUND AND OBJECTIVES Hospital-acquired legionnaires' disease can be prevented by disinfection of hospital water systems. This study assessed the long-term efficacy of copper-silver ionization as a disinfection method in controlling Legionella in hospital water systems and reducing the incidence of hospital-acquired legionnaires' disease. A standardized, evidence-based approach to assist ho...

متن کامل

CONTROLLING LEGIO!NELIA IN HOSPITAL WATERSYSTEMS: EXPERIENCE WITH THE SUPERHEAT-AND-FLUSH METHOD AND COPPER-SaVER IONIZATION

ORJECI1VE: To evaluate the effect of copper-silver ionization on Legionella colonization and nosocomial legionnaires' disease and to compare the efficacy of metal ions versus the superheat-and-tlush method of disinfection. DESIGN: Prospective determination over a 36-month period of copper and silver ion concentrations in the recirculating hotwater system, Legionella colonization of the hospital...

متن کامل

Negative effect of high pH on biocidal efficacy of copper and silver ions in controlling Legionella pneumophila.

Copper-silver (Cu-Ag) ionization has effectively controlled Legionella spp. in the hot water systems of numerous hospitals. However, it was ineffective at controlling Legionella in one Ohio hospital despite the confirmation of adequate total concentrations of copper and silver ions. The pH of the water at this hospital was found to be 8.5 to 9.0. The purpose of this study was to investigate the...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:
  • Clinical infectious diseases : an official publication of the Infectious Diseases Society of America

دوره 26 1  شماره 

صفحات  -

تاریخ انتشار 1998