Development in the protection scheme highlighting the issues based on two complementary protocols i.e., Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy (HSR). These two topologies could mitigate the issue of redundancy to a large extent by building this feature within the protection scheme. It overcomes a link or a switch or a node failure during a zero switchover or delay time. Further, issues arising due to single port failure and interoperability issues related to multi-vendor equipment could be addressed better in IEC 62439-2 published in 2010 taking into account all the shortcomings of Ethernet network failures of a digital protection scheme. In the protection scheme, the Intelligent Electronic Devices (IEDs) with Doubly Attached Node (DAN) components provide redundancy in protection with two active frames in the ring. PRP and HSR topologies not only provide means of redundancies in the protection scheme and communication network but also facilitate standardization of the Ethernet protocols that were vendor specific with number of interoperability issues.
منابع مشابه
Comparative Reliability Analysis of Substation Automation Architecture Based on IEC 61850 Standard
Using IEC 61850 standard would increase the reliability and availability of electricity network and put a huge impact on network automation. Even though much research works has been done in substation system reliability, there is a few works in automated substation control system reliability. This paper evaluates the reliability of substation automation system based IEC 61850 comparatively cons...
متن کاملReliability and Availability Investigation for Next- Generation Substation Function Based on IEC 61850
During the last years utilities have been facing a strong trend towards new technologies and standards. The most significant task is to fundamentally transform the capabilities and bring new solutions that support better power quality supply. Standardization solution IEC 61850 in terms of protection, monitoring and control functions is a promising solution that provides a great impact on substa...
متن کاملDependability Optimization of Process-level Protection in an IEC-61850-Based Substation
Power substations are intensively renovated toward using information and communication technologies such as object oriented modeling and Ethernet networks. In the last two decades, Substation automation systems used capabilities of network communication services adopted from sophisticated international standardizations such as IEC 61850. Distributed safety related functions take advantage of th...
متن کاملMACsec Layer 2 Security in HSR Rings in Substation Automation Systems
The smart-grid concept takes the communications from the enclosed and protected environment of a substation to the wider city or nationwide area. In this environment, cyber security takes a key role in order to secure the communications. The challenge is to be able to secure the grid without impacting the latency while, at the same time, maintaining compatibility with older devices and non secu...
متن کاملCase Study: Revised Engineering and Testing Practices Resulting From Migration to IEC 61850
Replacing hardwired connections with digital communications over Ethernet requires new engineering and testing practices. PPL Electric Utilities Corporation (PPL) recently designed, installed, and tested a new high-voltage substation using next-generation relay and control equipment. This next-generation substation (NGS) is based on networked Ethernet intelligent electronic devices (IEDs) commu...