This paper presents wavelet based islanding detection in distributed generation (DG) interfaced to the microgrid. Also a new fast method is developed for islanding detection based on measuring the utility currents and voltages signals processed by discrete wavelet transform. These currents and voltages signals are measured before the main circuit breaker of microgrid network and their features extracted by discrete wavelet transform. These features are sum of wavelet coefficients energy and are used for distinguishing the islanding conditions from non-islanding ones. Because of changing in measuring point of currents and voltages signals from point of common coupling (PCC) in traditional methods to before the main circuit breaker in proposed method, this new method detects the islanding conditions faster than the other methods. The proposed method has been examined under various scenarios; including mains supply faults, various one, two, or three phases' grid faults, and changes of rate of produced energy on IEEE 1547 anti-islanding test system. The numerical studies show the feasibility and applicability of the proposed method with satisfactory results.
منابع مشابه
Islanding Detection Method of Distributed Generation Based on Wavenet
Due to the increasing need to distributed energy resources in power systems, their problems should be studied. One of the main problem of distributed energy resources is unplanned islanding. The unplanned islanding has some dangers to the power systems and the repairman which are works with the incorrect devices. In this paper, a passive local method is proposed. The proposed method is based on...
متن کاملA Novel Passive Method for Islanding Detection in Microgrids
Integration of distributed generations (DGs) in power grids is expected to play an essential role in the infrastructure and market of electrical power systems. Microgrids are small energy systems, capable of balancing captive supply and requesting resources to retain stable service within a specific boundary. Microgrids can operate in grid-connected or islanding modes. Effective islanding detec...
متن کاملIslanding Detection in Distributed Generations Using Negative Sequence Components
In this paper negative sequence components are used for islanding detection in distributed generation (DG) based system. In this approach, the negative sequence component of the voltage and current signals are analyzed through wavelet transform. The detailed coefficient d1 clearly identifies the event and thus detects the islanding condition. The change in energy and standard deviations of wave...
متن کاملتعیین ناحیه غیر قابل تشخیص و تشخیص جزیره ای شدن تطبیقی واحدهای تولید پراکنده اینورتری جریان ثابت
In this paper, at first, the non-detection zones (NDZ) of under/over voltage relay have been determined for constant current inverter based DG and then, an islanding detection method is presented using this relay. In the presented method, the DG direct current reference has a fixed value in normal condition, if the point of common coupling (PCC) voltage changes, Idref is determined as a linear ...
متن کاملارایه روشی ترکیبی نوین بر اساس نسل دوم تبدیل موجک و روش جابجایی فرکانس ساندیا برای تشخیص کارکرد جزیره ای در تولیدات پراکنده مبتنی بر اینورتر
This paper is introducing a new controlling scheme with second generation wavelet transform and sandia frequency shift (SFS) for islanding detection of inverter-based distributed generation. This new hybrid method combines two active and passive methods through two performance zones. The new hybrid method calculates energy entropy of wavelet coefficients in its passive zone and if it increases ...