An active islanding detection method without destabilizing the system gives the advantage of accurate decision and the capability to keep the micro-grid energized while islanding occurs. Harmonic and perturbation current injection are such active methods, but none in the literature has discussed about islanding detection in multi-inverter systems. This paper proposes an active islanding detection method for multiinverter systems which works based on perturbation of direct (d-) and quadrature (q-) axis reference currents of inverters. The perturbations are synchronized according to voltage phase at point of common coupling (PCC) to avoid interaction. The q-axis voltage at PCC is considered as the output of system and the frequency response (FR) of system is obtained analytically for normal and island modes. The results show that the FR of system especially its phase has a noticeable difference in normal and island modes, which islanding can be detected by comparing the phase of system FR with a proper threshold. At the end, the analytical results are confirmed by some simulations using the software PSCAD/EMTDC. © 2015 Elsevier B.V. All rights reserved.
منابع مشابه
Inverter based distributed generator islanding detection method using U/O voltage relay
Islanded operation of distributed generators is a problem that can take place when they are connected to a distribution system. In this paper an islanding detection method is presented for inverter based distributed generation (DG) using under/over voltage relay. The method is an adaptive one and is based on the change of DG active power reference (Pref) in inverter control interface. The activ...
متن کاملتعیین ناحیه غیر قابل تشخیص و تشخیص جزیره ای شدن تطبیقی واحدهای تولید پراکنده اینورتری جریان ثابت
In this paper, at first, the non-detection zones (NDZ) of under/over voltage relay have been determined for constant current inverter based DG and then, an islanding detection method is presented using this relay. In the presented method, the DG direct current reference has a fixed value in normal condition, if the point of common coupling (PCC) voltage changes, Idref is determined as a linear ...
متن کاملIslanding Detection Method for Multi-Inverter Distributed Generation
Islanding detection is an essential function for safety and reliability in grid-connected distributed generation (DG) systems. Several methods for islanding detection are proposed, but most of them may fail under multi-source configurations, or they may produce important power quality degradation which gets worse with increasing DG penetration. This paper presents an active islanding detection ...
متن کاملMicrogrid Islanding Detection Method based on Frequency - Reactive Power Feedback
Islanding detection is one of the essential features for photovoltaic grid-connected systems; detection performance is directly related to safe operation of the equipment. Summarize existing islanding detection, then an active method based on frequency – reactive power feedback islanding detection is proposed. Once an islanding condition occurs, the method introducing a load frequency reactive ...
متن کاملFuzzy Controller Based 3-phase Inverter for Micro Grid with Induction Motor Drive Application
In this paper author discussed PI and fuzzy controllers with the three phase inverter concept and this converter connected to induction motor drive as load. This presents a unified control strategy that enables both islanded and grid-tied operations of three-phase inverter in distributed generation, with no need for switching between two corresponding controllers or critical islanding detection...