Frequency Tracking ih Power Networks in the Presence of Harmonics
نویسندگان
چکیده
Three new techniques for frequency measurement are proposed in the paper. The first is a modified zero crossing method using curve fitting of voltage samples. The second method is based on polynomial fitting of the DFT quasistationary phasor data for calculation of the rate of change of the positive sequence phase angle. The third method o p erates on a complex signal obtained by the standard technique of quadrature demodulation. All three methods are characterized by immunity to reasonable amounts of noise and harmonics in power systems. The performance of the proposed techniques is illustrated on several scenarios by computer simulation.
منابع مشابه
Optimal Estimation of Harmonic Components Using ISFLA
In this paper a novel method based on evolutionary algorithms is presented to estimate the harmonic components. In general, the optimization of the harmonic estimation process is a multi-component problem, in which evaluation of the phase and harmonic frequency is the nonlinear part of the problem and is solved based on the mathematical and evolutionary methods; while estimation of amplitude of...
متن کاملDesing And Implementation of Adaptive Active Filters for Exact Estimation And Elimination of AC Network Distortions
In recent years, active filters have been considered and developed for elimation of harmonics in power networks. Comparing with passive, they are smaller and have better compensating characteristics and resistance to line distortions. In this paper, a novel idea based on adaptive filter theory in presented to develop an active filter to eliminate the distortions of an arbitrary signal. Using th...
متن کاملDesing And Implementation of Adaptive Active Filters for Exact Estimation And Elimination of AC Network Distortions
In recent years, active filters have been considered and developed for elimation of harmonics in power networks. Comparing with passive, they are smaller and have better compensating characteristics and resistance to line distortions. In this paper, a novel idea based on adaptive filter theory in presented to develop an active filter to eliminate the distortions of an arbitrary signal. Using th...
متن کاملMathematical Analysis of Optimal Tracking Interval Management for Power Efficient Target Tracking Wireless Sensor Networks
In this paper, we study the problem of power efficient tracking interval management for distributed target tracking wireless sensor networks (WSNs). We first analyze the performance of a distributed target tracking network with one moving object, using a quantitative mathematical analysis. We show that previously proposed algorithms are efficient only for constant average velocity objects howev...
متن کاملA Coordinated Control Scheme for Improving Voltage Quality Using Power Electronics Interfaced DGs
Recently, increasing of non-linear loads in the power distribution network has been increased harmonics in these networks. The harmonics problems get worse and complicated by installation of power factor correction capacitors and filters. But the Distributed Generations (DGs) interface inverters with properly control can help to improve power quality, harmonic compensation and voltage unbalance...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
دوره شماره
صفحات -
تاریخ انتشار 2004