Protection setting in 2x25 kV 50 Hz railway traction systems by digital simulation
نویسندگان
چکیده
In this paper, after a short description of the problems related to the detection of short circuits in 2x25 kV 50 Hz traction systems, a methodology for the choice of the operating area of the relay for protections based on the comparison between a measured line impedance and a fixed minimum impedance is presented. The proposed methodology has been realized through the development of a procedure for the automatic management of the simulation of a given electric system, considering different failure positions and different types of failures. Various software tools have been utilized: -ATP (DOS version of EMTP) for the modelling and simulation of electric networkso; -macroinstruction systems for the management and the automatic editing of files, for the automation of iterative simulations related to different parameters, for a numerical processing of data and for a graphic management of results. Finally, the results obtained for a section of a high speed double track railway system are reported; they refer to a situation in which a neighbouring substation is assumed to be out of order.
منابع مشابه
An integrated methodology for 2 x 25 kV , 50 Hz traction system calculation
The paper describes an integrated calculation methodology which, by simulating railway traffic, allows analysis of the performance of 2x25 kV 50 Hz electric traction systems. This methodology performs a multiconductor electrical analysis of the traction circuit utilising ATP-EMTP software (Alternative Transient Program-Electromagnetic Transient Program) and therefore additionally allows calcula...
متن کاملSteady State and Transient Short Circuit Analysis of 2x25 kV High Speed Railways
In the paper, a detailed model for the short circuit analysis of the AC 2x25 kV-50 Hz traction system has been derived and implemented. Two different methods have been used: the time domain and frequency domain approaches. The two approaches are discussed and numerical applications are reported. In particular, in order to assess the feasibility of both the two methodologies, the results have be...
متن کاملRecent results on the Power Quality of Italian 2x25 kV 50 Hz railways
The recordings of the pantograph voltage and current waveforms across Italian and French high speed railway lines (both Autotransformer 2x25 kV 50 Hz systems) are analyzed to estimate some Power Quality indexes: harmonic spectra, harmonic distortion, displacement factor and fundamental component, in various rolling stock operating conditions. These indexes, that define the electrical interface ...
متن کاملMeasurements on 25 kV Traction Power Supply Systems
At the moment 25 kV traction power supply systems are being introduced in the Netherlands. Currently in the Netherlands a 1500 V DC system is used, however due to increasing energy demands this system is no longer sufficient. For the high-speed lines and heavy freight lines, which are under construction, the 2x25 kV AC system has been chosen. Introduction of this new technology leads to differe...
متن کاملSimplified model and submodule capacitor voltage balancing of single-phase AC/AC modular multilevel converter for railway traction purpose
A single-phase AC/AC modular multilevel converter (MMC) can interact directly with 25 kV railway grid without a bulky 50 Hz step-down transformer. This brings in great savings in size and cost. Submodule (SM) voltage balancing of this kind of MMCs remains a major technique issue. This study proposes a voltage-balancing solution for this scenario which consists of intraand inter-arm voltage bala...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
دوره شماره
صفحات -