Development and characterization of an inclined quad-vortex range hood.

نویسندگان

  • Rong Fung Huang
  • Jia-Kun Chen
  • Ji-Heng Lee
چکیده

In order to increase containment efficiency and reduce energy consumption, an inclined quad-vortex range hood (IQV range hood) was developed and tested by experimental methods. The flow structure was observed by a laser-assisted flow visualization technique and laser Doppler velocimetry (LDV). Leakage characteristics were measured by the tracer gas (sulfur hexafluoride) detection method. By arranging a narrow suction slot on the bottom face of the hood and two side plates hanging under lateral faces of the hood, a flow field featuring four backwards-inclined vortical flow structures was formed at suction velocities of larger than about 10 m s(-1) (suction flow rate 7.2 m(3) min(-1)). Oil mists were coherently contained in the vortical flow structures without observable dispersion out of the vortices; they rose up spirally with inclination towards the rear wall and were inducted into the suction slot. The backwards inclination of the oil-mist-containing vortical flow structures, caused by the backwards offset arrangement of the suction slot and the Coanda effect, benefited from the reduction in pollutant leakage induced by the influence of a mannequin's presence. Experimental results using the tracer gas concentration detection method showed a close correlation with the results from the flow visualization and LDV measurements. Under both occupied and unoccupied conditions, in which the mannequin was either present or not present, the IQV range hood provided low SF6 leakage concentration levels.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Flow Characteristics and Robustness of an Inclined Quad-vortex Range Hood

A novel design of range hood, which was termed the inclined quad-vortex (IQV) range hood, was examined for its flow and containment leakage characteristics under the influence of a plate sweeping across the hood face. A flow visualization technique was used to unveil the flow behavior. Three characteristic flow modes were observed: convex, straight, and concave modes. A tracer gas detection met...

متن کامل

Development and characterization of an inclined air-curtain (IAC) fume hood.

An inclined air-curtain (IAC) fume hood was developed and characterized using the laser-assisted smoke flow visualization technique and tracer-gas (sulphur hexafluoride) concentration detection method. The IAC fume hood features four innovative design elements: (i) an elongated suction slot installed at the hood roof with an offset towards the rear wall, (ii) an elongated up-blowing planar jet ...

متن کامل

Flow characteristics of an inclined air-curtain range hood in a draft

The inclined air-curtain technology was applied to build an inclined air-curtain range hood. A draft generator was applied to affect the inclined air-curtain range hood in three directions: lateral (θ=0°), oblique (θ=45°), and front (θ=90°). The three suction flow rates provided by the inclined air-curtain range hood were 10.1, 10.9, and 12.6 m(3)/min. The laser-assisted flow visualization tech...

متن کامل

Flow and containment characteristics of a sash-less, variable-height inclined air-curtain fume hood.

To increase containment efficiency and reduce energy consumption, a sash-less, variable-height inclined air-curtain fume hood (sIAC hood) was developed and tested by a laser-assisted flow visualization technique and tracer-gas detection method. This novel design requires neither sash nor baffle. The sIAC hood employed the inclined push-pull air-curtain technique and two deflection plates instal...

متن کامل

Impact of Magnetic Field on Convective Flow of a Micropolar Fluid with two Parallel Heat Source

A numerical study is performed to analysis the buoyancy convection induced by the parallel heated baffles in an inclined square cavity. The two side walls of the cavity are maintained at a constant temperature. A uniformly thin heated plate is placed at the centre of the cavity. The horizontal top and bottom walls are adiabatic. Numerical solutions of governing equations are obtained using the ...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:
  • The Annals of occupational hygiene

دوره 57 9  شماره 

صفحات  -

تاریخ انتشار 2013